INTEGRATED FLAME SCANNER
with INTERNAL FLAME RELAY
Type 95IR / 95UV / 95DS
The FIREYE InSight Type 95IR, 95UV, and 95DS flame scanners are
micro-processor
based flame scanners utilizing solid state infrared (IR), ultraviolet
(UV)
or dual (IR and UV) sensors.
The FIREYE InSight Type 95 flame scanners incorporate an internal
flame
relay with adjustable ON/OFF thresholds, thereby eliminating the need
for
a remote flame amplifier.
All FIREYE InSight scanner models are powered by 24 Vdc, have a
twelve-pin
electrical quick-disconnect, and contain electronic self-checking (no
mechanical
shutter required). The scanners contain an eight character
alpha-numeric
LED display and a four push-button keypad to enable the user to view
operating
parameters and select setpoints.
INSIGHT SCANNER FEATURES
| Features |
Basic Models (S1)
|
Expanded Models (S2)
|
| |
95IR S1
|
95UV S1
|
95DS S1
|
95IR S2
|
95UV S2
|
95DS S2
|
| Infared Sensor |
|
|
|
|
|
|
| Ultraviolet Sensor |
|
|
|
|
|
|
| Flame Relay |
|
|
|
|
|
|
| Fault Relay |
|
|
|
|
|
|
| 4-20mA Output |
|
|
|
|
|
|
Modulation
Frequency Selections |
3
|
3
|
3
|
21
|
21
|
21
|
| Memory Files |
2
|
2
|
2
|
4
|
4
|
4
|
| Communications |
|
|
|
|
|
|
| AutoTune |
|
|
|
|
|
|
| Pre-Edit |
|
|
|
|
|
|
INSIGHT SCANNER DIMENSIONS
| MECHANICAL: |
|
| Housing Material: |
Cast aluminum with gray polyester powder coat finish |
| Housing Weight: |
3 1bs (1.41kg), flange additional 0.7 lbs (0.30kg) |
| Environmental: |
NEMA 4X |
| Mounting: |
Requires one of two threaded mounting flanges, ordered
separately (see
below) |
| Mounting Flanges: |
P/N 60-2673 - 1" NPT female pipe mount with 3/8" NPT
female cooling
air connection, includes 1"NPT x 3" long heat insulating nipple (P/N
35-127-1). |
| Mounting Flange Weight: |
0.7 lbs (0.32kg) |
| Cooling / Purge Air Requirements: |
Source: Clean, dry, cool
Volume: 4 SCFM (113 l/min) at 3/8" threaded mounting flange, or 1 inch
“Y” fitting,
mounted on scanner sight pipe. Temperature near the upper limit of
the scanner operating range and/or use with dirty/dusty fuels may
require
up to 15 SCFM (425 l/min).
Pressure: Adequate to overcome furnace or windbox pressure |
| Temperature Rating: |
-40° F to + 150°F (-40°C to +65°C) |
| Humidity: |
0% to 95% relative humidity, non-condensing |
ELECTRICAL: |
|
| Input Power: |
24 Vdc, +10%, -15% supply current 0.5 A |
| Electrical Connection: |
12-pin quarter-turn quick-disconnect |
| Relay Output: |
FLAME RELAY, SPST (N.O.)
FAULT RELAY, SPST (N.C.) |
| Contact Rating: |
Minimum: 10 mA @ 5 Vdc
Maximum: 2 A @ 240 Vac (resistive load)
2 A @ 30 Vdc (resistive load) |
| Analog Output: |
4-20 mA dc current, referenced to 24Vdc, maximum connected
load: 750
ohms |
| Status Indication: |
Eight (8) character alpha-numeric LED display (scrolling
capability) |
| Operator Interface: |
Four (4) pushbutton style keys |
| Cable Specification: P/N 59-497: |
Multi-core, 12 conductor (color coded), with overall braided
shield
Six #18 AWG and four #22 AWG conductors, plus one #22 AWG twisted pair
Cable Jacket: Irradiated Modified Polyolefin (flame-retardant, low
smoke, zero halogen)
Nominal O.D. 0.45" (11.4 mm)
Maximum O.D. 0.47" (11.9 mm)
Maximum cable length 1000 feet (305 meters) |